Counterflow and Crossflow Film Fills
 
   Cross-Fluted
 

CF1900MA Cross-Fluted Film Fill Media

 

        

AccuPac® Cross Fluted Fills improve water distribution by splitting the water stream as it descends through the fill pack. The CF1900 MA splits the water stream 8 times in a 12” (305 mm) vertical path. High thermal performance (high KaV/L) and low pressure drop are simultaneously achieved through engineered flute/microstructure design and the highest manufacturing standards.

 

Features and Benefits

• Patented “MA” (Mechanical Assembly) Technology for glue-free packs that can be assembled on-site
• Bonded edge with dedicated bond points for added durability
• Engineered microstructure for improved water distribution and thermal mixing
• High thermal performance
• Improved water distribution
• Proprietary edge trim that directs water to both sides of sheet
• Material meets Cooling Tower Institute (CTI) Standard 136
• Available in PVC, HPVC, and Polypropylene

    

 

Applications

The CF1900MA is the popular choice for field-erected or package counterflow cooling towers. Can also be used in crossflow towers. For use in Power, Refining, Chemical, Steel, and Food Processing applications where water quality is “average-to-good”.

 

Product Dimensions

SURFACE AREA SHEET SPACING FLUTE ANGLE SHEETS PER FT. MEDIA PACK SIZES:
Depth (D), Width (W), Length (L)
Minimum Maximum Standard
48 ft2/ft3
(157.5 m2/m3)
19 mm 30° 16 D: 12 in
(305 mm)
W: 6 in
(153 mm)
L: 1 ft
(305 mm)
D: 24 in
(610 mm)
W: 24 in
(610 mm)
L: 10 ft
(3050 mm)
D: 12 in (305 mm) or
24 in (610 mm)
W: 12 in (305 mm) or
24 in (610 mm)
L: 4 ft (1220 mm),
6 ft (1829 mm),
8 ft (2439 mm) or
10 ft (3048 mm)

 

Product Weights

NOMINAL GAUGE DRY WEIGHT
mils mm lbs/ft3 kg/m3
10 0.25 1.8 28.8
15 0.38 2.6 41.6

 

Brentwood sheet thicknesses are quoted in final gauge (as measured in field) of .008” (.203 mm), .010” (.254 mm), .015 (.381 mm), or your specific requirement. All Brentwood fill products are available in PVC and are UV stabilized. The PVC compounds used in Brentwood fills have outstanding resistance to weather exposure and are nearly impervious to chemical degradation by alkali, acids, greases, fats, oils, and biological attack. Brentwood PVC has excellent fire rating due to its self-extinguishing characteristics, and meets or exceeds Cooling Tower Institute Standard 136. HPVC (high temperatures), PP (polypropylene), and ABS plastics are also available for special applications.

 


 

CF1900MA Cross-Fluted Film Fill Media

 

        

AccuPac® Cross Fluted Fills improve water distribution by splitting the water stream as it descends through the fill pack. The CF1200 MA splits the water stream 10 times in a 11.8” (300 mm) vertical path. High thermal performance (high KaV/L) and low pressure drop are simultaneously achieved through engineered flute/microstructure design and the highest manufacturing standards.

 

Features and Benefits

Bevel Tips(see right) promotes drainage at fill pack interfaces. Note: Packs are always installed with Bevel Tips at bottom of pack.
•Patented "MA"(Mechanical Assembly) Technology for glue-free packs.

• Engineered microstructure for improved water distribution and thermal mixing
• High thermal performance
• Improved water distribution
• Proprietary edge trim that directs water to both sides of sheet
• Material meets Cooling Tower Institute (CTI) Standard 136
• Available in PVC and HPVC

    

 

Applications

The CF1200MA is for use in package counterflow towers (HVAC and light industrial applications) and as a distribution pad in 3.9 " and 5.9 " depths. Water quality must be "good to very good". Distribution pads will be supplied as a Solvent Bonded
product.

 

Product Dimensions

SURFACE AREA SHEET SPACING FLUTE ANGLE SHEETS PER FT. MEDIA PACK SIZES:
Depth (D), Width (W), Length (L)
Minimum Maximum Standard
69 ft2/ft3
(226 m2/m3)
12 mm 30° 26 D: 3.9 in
(100 mm)
W: 6 in
(153 mm)
L: 1 ft
(305 mm)
D: 11.8 in
(300 mm)
W: 12 in
(305 mm)
L: 10 ft
(3048 mm)
D: 11.8 in (300 mm)
W: 12 in (305 mm)
L: 4 ft (1220 mm),
6 ft (1829 mm),
8 ft (2439 mm) or
10 ft (3048 mm)

 

Product Weights

NOMINAL GAUGE DRY WEIGHT
mils mm lbs/ft3 kg/m3
8 0.20 2.5 38.4
10 0.25 2.9 44.8

Brentwood sheet thicknesses are quoted in final gauge (as measured in field) of .008” (.203 mm), .010” (.254 mm), .015 (.381 mm), or your specific requirement. All Brentwood fill products are available in PVC and are UV stabilized. The PVC compounds used in Brentwood fills have outstanding resistance to weather exposure and are nearly impervious to chemical degradation by alkali, acids, greases, fats, oils, and biological attack. Brentwood PVC has excellent fire rating due to its self-extinguishing characteristics, and meets or exceeds Cooling Tower Institute Standard 136. HPVC (high temperatures), PP (polypropylene), and ABS plastics are also available for special applications.

 


 

 

 

   Offset Vertical
 

 

OF21MA Offset Vertical Film Fill Media

 

        

AccuPac® Offset Vertical Fill combines the low-fouling characteristics of vertical flow with the enhanced water distribution of our cross-fluted designs. The OF21MA’s high KaV/L thermal performance and low pressure drop are similar to the CF1900/CF1900MA design, but with lower potential for fouling.

 

Features and Benefits

• High thermal performance.
• Lower fouling potential.
• Bonded edge with dedicated bond points for added durability
• Adhesive-free Mechanical Assembly (MA) technology is environmentally-friendly and allows fill packs to be assembled on-site without glue
• Proprietary edge cutting technology produces square packs that efficiently direct water to both sides of sheet
• Materials meet Cooling Tower Institute (CTI) Standard 136
• Available in PVC, HPVC, and Polypropylene

        

 

Applications

The OF21 MA is for use in counterflow cooling towers (field-erected and package installations) in Power, Refining, Chemical, Steel, and Food Processing applications where water quality is “average”.

 

Product Dimensions

SURFACE AREA SHEET SPACING FLUTE ANGLE SHEETS PER FT. MEDIA PACK SIZES:
Depth (D), Width (W), Length (L)
Minimum Maximum Standard
45 ft2/ft3
(147.8 m2/m3)
21 mm NA 14.7 D: 11.8 in
(300 mm)
W: 5 in
(127 mm)
L: 1 ft
(305 mm)
D: 23.8 in
(605 mm)
W: 18 in
(458 mm)
L: 10 ft
(3050 mm)
D: 11.8 in (300 mm) or
23.6 in (600 mm)
W: 18 in (458 mm)
L: 4 ft (1220 mm),
6 ft (1829 mm),
8 ft (2439 mm) or
10 ft (3048 mm)

 

Product Weights

NOMINAL GAUGE DRY WEIGHT
mils mm lbs/ft3 kg/m3
10 0.25 1.7 27.2
15 0.38 2.4 38.4

 

Brentwood sheet thicknesses are quoted in final gauge (as measured in field) of .008” (.203 mm), .010” (.254 mm), .015 (.381 mm), or your specific requirement. All Brentwood fill products are available in PVC and are UV stabilized. The PVC compounds used in Brentwood fills have outstanding resistance to weather exposure and are nearly impervious to chemical degradation by alkali, acids, greases, fats, oils, and biological attack. Brentwood PVC has excellent fire rating due to its self-extinguishing characteristics, and meets or exceeds Cooling Tower Institute Standard 136. HPVC (high temperatures), PP (polypropylene), and ABS plastics are also available for special applications.

 

 

   Vertical Flow
 

 

VF19 PLUS  Vertical Flow Film Fill Media

 

        

AccuPac® Vertical Flow Fills feature vertical flow channels with large openings that produce the higher water velocities necessary to create an anti-fouling environment in the fill. In the VF19 PLUS we’ve added an engineered micro-structure to the flutes to improve water distribution and thermal mixing.

 

Features and Benefits

• Anti-fouling vertical flow design plus engineered microstructure for high water velocity and improved water distribution and thermal mixing
• Bonded edge with dedicated bond points for added durability
• Proprietary edge cutting technology produces square packs that efficiently direct water to both sides of sheet
• Material meets Cooling Tower Institute (CTI) Standard 136

        

 

Applications

The VF19 PLUS is for use in counterflow cooling towers where water quality is “poor” (poor make-up water or process contamination). Typical applications are Power, Refining, Chemical, Mining, and Food Processing. Because a cooling tower spray system’s washing effect reduces the fouling potential of the top 12” (300mm) of fills, a top layer of OF21MA or CF1900/CF1900MA should be considered to improve overall performance.

 

Product Dimensions

SURFACE AREA SHEET SPACING FLUTE ANGLE SHEETS PER FT. MEDIA PACK SIZES:
Depth (D), Width (W), Length (L)
Minimum Maximum Standard
47 ft2/ft3
(154 m2/m3)
19 mm 16 D: 11.8 in
(300 mm)
W: 6 in
(153 mm)
L: 1 ft
(305 mm)
D: 35.4 in
(900 mm)
W: 24 in
(610 mm)
L: 12 ft
(3660 mm)
D: 23.6 in (600 mm)
W: 12 in (305 mm) or
24 in (610 mm)
L: 4 ft (1220 mm),
6 ft (1829 mm),
8 ft (2439 mm). or
10 ft (3048 mm)

 

Product Weights

NOMINAL GAUGE DRY WEIGHT
mils mm lbs/ft3 kg/m3
10 0.25 1.7 27.2
15 0.38 2.5 40.0

 

Brentwood sheet thicknesses are quoted in final gauge (as measured in field) of .008” (.203 mm), .010” (.254 mm), .015 (.381 mm), or your specific requirement. All Brentwood fill products are available in PVC and are UV stabilized. The PVC compounds used in Brentwood fills have outstanding resistance to weather exposure and are nearly impervious to chemical degradation by alkali, acids, greases, fats, oils, and biological attack. Brentwood PVC has excellent fire rating due to its self-extinguishing characteristics, and meets or exceeds Cooling Tower Institute Standard 136. HPVC (high temperatures), PP (polypropylene), and ABS plastics are also available for special applications.

 


 

 

VF3800 Vertical Flow Film Fill Media

 

        

AccuPac® Vertical Flow Fills feature vertical flow channels with large openings that produce the higher water velocities necessary to create an anti-fouling environment in the fill.

 

Features and Benefits

• Larger flute openings and no flute microstructure for maximum water velocity
• Bonded edge with dedicated bond points for added durability
• Proprietary edge cutting technology produces square packs that efficiently direct water to both sides of sheet
• Material meets Cooling Tower Institute (CTI) Standard 136

        

 

Applications

The VF3800 has larger (38mm) flute oppenings and no microstructure for use in counterflow cooling towers where water quality is “poor” (poor make-up water or process contamination). Typical applications are Power, Refining, Chemical, Mining, and Food Processing.

 

Product Dimensions

SURFACE AREA SHEET SPACING FLUTE ANGLE SHEETS PER FT. MEDIA PACK SIZES:
Depth (D), Width (W), Length (L)
Minimum Maximum Standard
40 ft2/ft3
(131 m2/m3)
38 mm 16 D: 24 in
(610 mm)
W: 6 in
(153 mm)
L: 1 ft
(305 mm)
D: 24 in
(610 mm)
W: 24 in
(610 mm)
L: 12 ft
(3660 mm)
D: 24 in (610 mm)
W: 12 in (305 mm) or
24 in (610 mm)
L: 4 ft (1220 mm),
6 ft (1829 mm),
8 ft (2439 mm) or
10 ft (3048 mm)

 

Product Weights

NOMINAL GAUGE DRY WEIGHT
mils mm lbs/ft3 kg/m3
23/15 0.58/0.38 3.0 48.1
18/12 0.46/0.30 2.3 36.8

 

Brentwood sheet thicknesses are quoted in final gauge (as measured in field) of .008” (.203 mm), .010” (.254 mm), .015 (.381 mm), or your specific requirement. All Brentwood fill products are available in PVC and are UV stabilized. The PVC compounds used in Brentwood fills have outstanding resistance to weather exposure and are nearly impervious to chemical degradation by alkali, acids, greases, fats, oils, and biological attack. Brentwood PVC has excellent fire rating due to its self-extinguishing characteristics, and meets or exceeds Cooling Tower Institute Standard 136. HPVC (high temperatures), PP (polypropylene), and ABS plastics are also available for special applications.

 

 

 

   Cross Flow Herringbone
 

   

XF75 Cross Flow Herringbone Film Fill Media

 

        

AccuPac® Cross Flow Herringbone Fill uses a “herringbone” surface design engineered to distribute water evenly over the entire fill area for high thermal performance. Herringbone fills with integrated Inlet Louvers (XF75 IL) and Drift Eliminators (XF75 ID) complete this efficient, high-performance, crossflow media system.

 

Features and Benefits

• Superior air/water management for high thermal performance
• Engineered “herringbone” surface (left) for even water distribution
• Honeycomb bonded edges on the air inlets and outlets
• Interlocking offsets space the sheets and form a pack that is strong enough to be stacked one on top of the other in towers with fill heights over 10 ft (3050 mm). In these applications, Brentwood recommends the use of AccuGrid panels at the interface.
Bottom-supported for durability and ease of installation

        

 

Applications

The XF75 is designed on a 5° angle for easy installation in package crossflow towers (for HVAC and general industrial use).

 

 

Product Dimensions

SURFACE AREA SHEET SPACING FLUTE ANGLE SHEETS PER FT. MEDIA PACK SIZES:
Depth (D), Width (W), Length (L)
Minimum Maximum Standard
51 ft2/ft3
(167.4 m2/m3)
19 mm NA 16 D: 12 in
(305 mm)
W: 6 in
(153 mm)
L: 2 ft
(610 mm)
D: 24 in
(610 mm)
W: 12 in
(305 mm)
L: 10 ft
(3050 mm)
D: 24 in (610 mm)
W: 12 in (305 mm)
L: 4 ft (1220 mm),
6 ft (1829 mm),
8 ft (2439 mm) or
10 ft (3048 mm)
Standing Height (H) = L x .996

 

Product Weights

NOMINAL GAUGE DRY WEIGHT
mils mm lbs/ft3 kg/m3
10 0.25 1.7 27.2
15 0.38 2.4 38.4

 

Brentwood sheet thicknesses are quoted in final gauge (as measured in field) of .008” (.203 mm), .010” (.254 mm), .015 (.381 mm), or your specific requirement. All Brentwood fill products are available in PVC and are UV stabilized. The PVC compounds used in Brentwood fills have outstanding resistance to weather exposure and are nearly impervious to chemical degradation by alkali, acids, greases, fats, oils, and biological attack. Brentwood PVC has excellent fire rating due to its self-extinguishing characteristics, and meets or exceeds Cooling Tower Institute Standard 136. HPVC (high temperatures), PP (polypropylene), and ABS plastics are also available for special applications.

 


 

   

XF75 IL Cross Flow Herringbone Film Fill Media

with Integrated Inlet Louver

 

        

AccuPac® Cross Flow Herringbone Inlet Louver Fills combine an inlet louver with the high thermal performance of the XF75 herringbone cross flow fill pack.

 

Features and Benefits

• Integrated inlet louvers eliminate "splash out"
• Superior air/water management for high thermal performance
• Engineered “herringbone” surface for even water distribution
• Honeycomb bonded edges on the air inlets and outlets
• Interlocking offsets space the sheets and form a pack that is strong enough to be stacked one on top of another. In these applications (towers with fill heights over 10 ft [3050 mm]), Brentwood recommends the use of AccuGrid panels at the interface.
Bottom-supported for durability and ease of installation

        

 

Applications

The XF75 IL is an integrated inlet louver with fill section for use with XF75 media.

 

 

Product Dimensions

SURFACE AREA SHEET SPACING FLUTE ANGLE SHEETS PER FT. MEDIA PACK SIZES:
Depth (D), Width (W), Length (L)
Minimum Maximum Standard
51 ft2/ft3
(167.4 m2/m3)
19 mm NA 16 D: 24 in
(610 mm)
W: 6 in
(153 mm)
L: 2 ft
(610 mm)
D: 24 in
(610 mm)
W: 12 in
(305 mm)
L: 10 ft
(3050 mm)
D: 24 in (610 mm)
W: 12 in (305 mm)
L: 4 ft (1220 mm),
6 ft (1829 mm),
8 ft (2439 mm) or
10 ft (3048 mm)
Standing Height (H) = L x .996

 

Product Weights

NOMINAL GAUGE DRY WEIGHT
mils mm lbs/ft3 kg/m3
10 0.25 1.7 27.2
15 0.38 2.4 38.4

 

Brentwood sheet thicknesses are quoted in final gauge (as measured in field) of .008” (.203 mm), .010” (.254 mm), .015 (.381 mm), or your specific requirement. All Brentwood fill products are available in PVC and are UV stabilized. The PVC compounds used in Brentwood fills have outstanding resistance to weather exposure and are nearly impervious to chemical degradation by alkali, acids, greases, fats, oils, and biological attack. Brentwood PVC has excellent fire rating due to its self-extinguishing characteristics, and meets or exceeds Cooling Tower Institute Standard 136. HPVC (high temperatures), PP (polypropylene), and ABS plastics are also available for special applications.

 


 

   

XF75 ID Cross Flow Herringbone Film Fill Media

with Integrated Drift Eliminator

 

        

AccuPac® Cross Flow Herringbone Drift Eliminator Fills combine a drift eliminator with the high thermal performance of the XF75 herringbone cross flow fill pack.

 

Features and Benefits

• Integrated Drift Eliminators eliminate drift loss
• Superior air/water management for high thermal performance
• Honeycomb bonded edges on the air inlets and outlets
• Interlocking offsets space the sheets and form a pack that is strong enough to be stacked one on top of another. In these applications (towers with fill heights over 10 ft [3050 mm]), Brentwood recommends the use of AccuGrid panels at the interface.
• Engineered “herring bone” surface for even water distribution
Bottom-supported for durability and ease of installation

        

 

Applications

The XF75ID is an integrated drift eliminator with fill section for use with XF75 media. Other drift eliminators can be added for ultra-low drift loss.

 

 

Product Dimensions

SURFACE AREA SHEET SPACING FLUTE ANGLE SHEETS PER FT. MEDIA PACK SIZES:
Depth (D), Width (W), Length (L)
Minimum Maximum Standard
51 ft2/ft3
(167.4 m2/m3)
19 mm NA 16 D: 24 in
(610 mm)
W: 6 in
(153 mm)
L: 2 ft
(610 mm)
D: 24 in
(610 mm)
W: 12 in
(305 mm)
L: 10 ft
(3050 mm)
D: 24 in (610 mm)
W: 12 in (305 mm)
L: 4 ft (1220 mm),
6 ft (1829 mm),
8 ft (2439 mm). or
10 ft (3048 mm)
Standing Height (H) = L x .996

 

Product Weights

NOMINAL GAUGE DRY WEIGHT
mils mm lbs/ft3 kg/m3
10 0.25 1.7 27.2
15 0.38 2.4 38.4

 

Brentwood sheet thicknesses are quoted in final gauge (as measured in field) of .008” (.203 mm), .010” (.254 mm), .015 (.381 mm), or your specific requirement. All Brentwood fill products are available in PVC and are UV stabilized. The PVC compounds used in Brentwood fills have outstanding resistance to weather exposure and are nearly impervious to chemical degradation by alkali, acids, greases, fats, oils, and biological attack. Brentwood PVC has excellent fire rating due to its self-extinguishing characteristics, and meets or exceeds Cooling Tower Institute Standard 136. HPVC (high temperatures), PP (polypropylene), and ABS plastics are also available for special applications.

 

 

 

 
 
  Home | Cooling Tower Services | Parts & Accessories | News & Articles | Employment Opportunities | Contact  
Privacy Statement | Terms Of Use | Login | Register  
Design by Houston Web Design